Brainchild-E62-PID-Temperature-Controller- product

gafereview & Ọdịdị

Brainchild-E62-PID-Temperature-Controller- (2)

Igodo na ihe ngosi

Arụ ọrụ igodo

Igodo mpịakọta: Brainchild-E62-PID-Temperature-Controller- (3)
A na-eji igodo a họrọ oke ka ọ bụrụ viewed ma ọ bụ gbanwee.

Igodo elu/Mbawanye:Brainchild-E62-PID-Temperature-Controller- (4)
A na-eji igodo a iji bulie uru nke oke ahọpụtara.

Igodo ala/Welata:  Brainchild-E62-PID-Temperature-Controller- (5)
A na-eji igodo a belata uru nke oke ahọpụtara.

Igodo SHIFT:Brainchild-E62-PID-Temperature-Controller- (6)
A na-eji igodo a:

  • Move to the digit of the selected parameter and change the value by using up or down key to increase or decrease the value.

Scroll Up: Brainchild-E62-PID-Temperature-Controller- (7)
A na-eji igodo abụọ apịkọrọ ọnụ mee:

  • Go to the previous parameter

Tọgharia: + Brainchild-E62-PID-Temperature-Controller- (8)
A na-eji igodo abụọ apịkọrọ ọnụ mee:

  • Weghachite ngosi na ihuenyo ụlọ.
  • Tọgharia oti mkpu ozugbo ewepụrụ ọnọdụ mkpu.
  • Kwụsị ụkpụrụ njikwa akwụkwọ ntuziaka, ọnọdụ ntugharị akpaaka ma ọ bụ ọnọdụ mmezi.
  • Hichapụ ozi njehie akpaaka ma ọ bụ nzikọrịta ozi.
  • Enter the manual control menu if a failure mode occurs.

Pịgharịa gaa na ala: Brainchild-E62-PID-Temperature-Controller- (9)
Two keys pressed synchronously directly go to the Manual control mode

Tinye igodo: Brainchild-E62-PID-Temperature-Controller- (3)
Pịa Brainchild-E62-PID-Temperature-Controller- (3) ma jide 5 sekọnd ma ọ bụ karịa ka:

  • Enter the Auto-Tuning mode. Brainchild-E62-PID-Temperature-Controller- (10) Ngosipụta ga-egosi.
  • Enter the manual control mode. Brainchild-E62-PID-Temperature-Controller- (11) Ngosipụta ga-egosi.
    Enter the setup menu mode. Brainchild-E62-PID-Temperature-Controller- (12)Ngosipụta ga-egosi.
  • Brainchild-E62-PID-Temperature-Controller- (13) Perform calibration of a selected parameter during the calibration procedure. The display will show

Ihe ngosi ngosi menu

E kewaa menu n'ime otu ise. Ha bụ ndị a:

  1. Ntinye njirimara
  2. Auto-Tuning Mode Menu
  3. NchNhr ụkpụrụ ntuziaka
  4. Nhazi menu
  5. Calibration Mode Menu

Brainchild-E62-PID-Temperature-Controller- (14)

  • Pịa Brainchild-E62-PID-Temperature-Controller- (3) for the next parameter ; Press Brainchild-E62-PID-Temperature-Controller- (3) na Brainchild-E62-PID-Temperature-Controller- (4) igodo ịlaghachi na paramita gara aga.
  • Pịa ma jideBrainchild-E62-PID-Temperature-Controller- (3) for 3.1 seconds, then let go to select auto tuning mode.
  • Pịa ma jide Brainchild-E62-PID-Temperature-Controller- (3)for 4.2 seconds, then let go, to select manual control mode.
  • Pịa ma jide Brainchild-E62-PID-Temperature-Controller- (3)for 5.3 seconds, then let go to select setup mode.
  • Pịa ma jide Brainchild-E62-PID-Temperature-Controller- (3) maka sekọnd 6.4, wee hapụzie ka ịhọrọ ọnọdụ nhazi.

Ntinye njirimara
Jiri Brainchild-E62-PID-Temperature-Controller- (3) key to enter basic menu parameters, and press  Brainchild-E62-PID-Temperature-Controller- (3) again to select SP1, SEL1~SEL8.
Pịa  Brainchild-E62-PID-Temperature-Controller- (3)Brainchild-E62-PID-Temperature-Controller- (4) ịlaghachi na nke gara aga.

Brainchild-E62-PID-Temperature-Controller- (15)

Auto-Tuning Mode
Pịa Brainchild-E62-PID-Temperature-Controller- (3) key 5 seconds to activate Auto-Tuning Mode

Brainchild-E62-PID-Temperature-Controller- (16)

NchNhr ụkpụrụ ntuziaka
Pịa Brainchild-E62-PID-Temperature-Controller- (3) key 3 seconds to execute the selected default program

Brainchild-E62-PID-Temperature-Controller- (17)

Enter Manual Control Mode; refer to Manual 6.1 & 6.8.2~6.8.4

Brainchild-E62-PID-Temperature-Controller- (18)

Nhazi menu
The setup menu has been categorized into eight categories.
They are listed as below.

  1. Isi NchNhr (bASE)
  2. NchNhr mmepụta (oUT)
  3. Communication Menu (CoMM)
  4. User Select Menu (SEL)

Isi NchNhr (bASE)
Jiri Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get bASE in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to basic menu parameters.

Brainchild-E62-PID-Temperature-Controller- (19)

NchNhr mmepụta (oUT)
Jiri Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get oUT in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to output menu parameters.

Brainchild-E62-PID-Temperature-Controller- (20)

Communication Menu (CoMM)
Jiri Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key to get CoMM in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to communication menu parameters.
Please note that confirm A2FN set to CoMM when using communication.

Brainchild-E62-PID-Temperature-Controller- (21)

User Select Menu (SEL)
Jiri Brainchild-E62-PID-Temperature-Controller- (4)orBrainchild-E62-PID-Temperature-Controller- (5) key get SEL in the lower display then use Brainchild-E62-PID-Temperature-Controller- (3) key to enter to select the user menu parameters.

Brainchild-E62-PID-Temperature-Controller- (22)

Ụdị nhazi

Brainchild-E62-PID-Temperature-Controller- (24)

Pịa Brainchild-E62-PID-Temperature-Controller- (3) key for 2 seconds or longer (not more than 3 seconds) ; then release it to enter calibration Mode.
Pịa Brainchild-E62-PID-Temperature-Controller- (3) key for 5 seconds to perform calibration

  • Please note that it is required to use specialized equipment to apply calibration, attempting to change will affect device accuracy

Mara:

  • Using Manual, Auto-Tuning, Calibration modes will break the control loop and change some of the previous setting data. Make sure that the system is allowable to apply these modes.
  • The flow chart shows a complete list of all parameters. For actual application, the number of available parameters will vary depending on the setup and model of the controller and will be less than that shown in the flow chart.
  • The user can select up to 8 parameters to put in the user select menu by using the SEL1~SEL8 parameters in the setup menu

Tupu ịmalite, Tọọ ntinye/mmepụta
Mgbe emelitere, pịa ma jide Brainchild-E62-PID-Temperature-Controller- (3) for 5.3 seconds, then let go to enter Setup Menu. Complete Parameter setting, INPT, UNIT, DP, O1TY, O1L and O1H.

  • Enter the Setup Menu. Press Brainchild-E62-PID-Temperature-Controller- (3) for 5 seconds to enter Basic Menu (bASE). Finish setting for INPT, UNIT and DP. Exit the level.
  •  Return to the Setup Menu. Press Brainchild-E62-PID-Temperature-Controller- (3) for 5 seconds to enter Output Menu (oUT). Finish setting for O1TY, O1L and O1H. Press and hold Brainchild-E62-PID-Temperature-Controller- (4) Brainchild-E62-PID-Temperature-Controller- (5)  ma laghachi na homepage.

Brainchild-E62-PID-Temperature-Controller- (25)

Okpokoro OP1L/OP1H

Oke OP1L OP1H
OM9A-3 4-20 20.0 100.0
OM9A-3 0-20 0.0 100.0
OM9A-5 0-5V 0.0 50.0
OM9A-5 1-5V 10.0 50.0
OM9A-5 0-10 0.0 100.0

* When O1TY as DC.MA or  DC. Vo, set the value based on usage requirement

Njikọ ọnụ

Brainchild-E62-PID-Temperature-Controller- (1)

Nkọwapụta oke

User Menu Parameter

Modbus Oke Nkọwa Oke Ọdabara Nweta
0 SP1 Tọọ ihe 1 Ala: SP1L

Ọnụ: SP1H

25.0 Celsius C R/W
64 PV Usoro uru Ala: -19999

elu: 45536

(77.0 Celsius F) R
65 SV Uru ihe atọrọ ugbu a Ala: SP1L

Ọnụ: SP1H

—— R
44  

SEL1

Họrọ paramita nke mbụ maka menu onye ọrụ 0 Ọ BỤGHỊ

1 A1SP

2 A2SP

3 Mkpọchi

4 INPT

5 PB

6 TI

7 TD

8 SHIF

9 OFST

10 O1HY

11 A1HY

12 A2HY

13 ADDR

—— R/W
45 SEL2 Select 2nd parameter Select 2nd parameter for user manual. Same as the SEL1 0 R/W
46 SEL3 Select 3rd parameter Select 3rd parameter for user manual. Same as the SEL1 0 R/W
47 SEL4 Select 4th parameter Select 4th parameter for user manual. Same as the SEL1 0 R/W
48 SEL5 Select 5th parameter Select 5th parameter for user manual. Same as the SEL1 0 R/W
49 SEL6 Select 6th parameter Select 6th parameter for user manual. Same as the SEL1 0 R/W
50 SEL7 Select 7th parameter Select 7th parameter for user manual. Same as the SEL1 0 R/W
51 SEL8 Select 8th parameter Select 8th parameter for user manual. Same as the SEL1 0 R/W

Manual Mode Parameter

Modbus Oke Nkọwa Oke Ọdabara Nweta
66 MV1 Mpụta 1% Uru Ala: 0.00

Elu: 100.00%

—- R (R/W,

Akwụkwọ ntuziaka)

Basic (bASE) Parameter

Modbus Oke Nkọwa Oke Ọdabara Nweta
3 Mkpọchi Họrọ paramita a ga-akpọchi 0 Ọ dịghị: Ọ dịghị oke ihe akpọchiri

1  SEt: Setup data are locked

2 uSEr: Setup data and user data are locked. SetPoint are unlocked.

3  ALL: All data are locked

0 R/W
4 INPT Input sensor selec- tion 0 J_tC: J ụdị Thermocouple

1 K_tC: K ụdị Thermocouple

2 t_tC: T type Thermocouple

3 R_tC: R ụdị Thermocouple

4 S_tC: S type Thermocouple

5 Pt. dN: PT 100 DIN

6 Pt.JS: PT 100 JIS

1 R/W
5 UNIT Nhọrọ nkeji ntinye 0 oC: °C unit

1 oF: °F unit

0 R/W
6 DP Decimal point selec- tion 0 No.dP: no decimal point

1 1-dP: 1 nkeji iri

 

1

 

R/W

 

9

 

SP1L

Oke dị ala nke uru ntụpọ atọrọ Ala:

J_TC: -120.0°C (-184.0°F)

K_TC: -200.0°C (-328.0°F)

T_TC: -250.0°C (-418.0°F) R_TC: 0.0°C ( 32.0°F) S_TC: 0.0°C ( 32.0°F) PTDN: -200.0°C (-328.0°F)

PTJS: -200.0°C (-328.0°F)

Ọnụ: SP1H

-17.8 Celsius

(0.0 Celsius F)

 

R/W

10  

SP1H

Oke dị elu nke uru ihe setịpụrụ Ala: SP1L

Elu:

J_TC: 1000.0°C (1828.0°F) K_TC: 1370.0°C (2498.0°F) T_TC: 400.0°C ( 752.0°F) R_TC: 1767.7°C (3214.0°F) S_TC: 1767.7°C (3214.0°F) PTDN: 850.0°C (1562.0°F) PTJS: 600.0°C (1112.0°F)

537.8 Celsius C

(1000.0 Celsius F)

 

R/W

12 MGBE  

Nyo damping time constant of PV

0 0: 0 nkeji oge na-adịgide adịgide

1 0.2: 0.2 nkeji oge na-adịgide adịgide

2 0.5: 0.5 nkeji oge na-adịgide adịgide

3 1: 1 nkeji oge na-adịgide adịgide

4 2: 2 nkeji oge na-adịgide adịgide

5 15: 5 nkeji oge na-adịgide adịgide

6 10: 10 nkeji oge na-adịgide adịgide

7 20: 20 nkeji oge na-adịgide adịgide

8 30: 30 nkeji oge na-adịgide adịgide

9 60: 60 nkeji oge na-adịgide adịgide

2 R/W
14 PB Oke bandwit

uru

Ala: 0.0

Elu: 500.0°C (900.0°F)

10.0 Celsius C

(18.0 Celsius F)

R/W
15 TI Ọnụ ahịa oge ọnụ Low: 0, High: 3600 sec 60 R/W
16 TD Uru oge ewepụtara Low: 0, High: 360.0 sec 30.0 R/W
11 SHIF PV shift (offset)

uru

Low: -200.0°C (-360.0°F) High: 200.0°C (360.0°F) 0.0 Celsius C

(0.0 Celsius F)

R/W
68 CICF Mgbanwe nzacha CIC 0 Gbanyụọ

1 NA

0 R

Output (oUT) Parameter

Modbus Oke Nkọwa Oke Ọdabara Nweta
17 ỌPỌ1 Mmepụta 1 ọrụ 0 REVR: Reverse (heating) control action

1 dIRt: Direct (cooling) control action

0 R/W
21 CYC1 Mmepụta 1 okirikiri oge Low: 0.1;

Elu: 90.0 sk.

18.0 R/W
18 O1TY Ụdị mgbama 1 mmepụta 0 RELY: Mmepụta mbugharị

1 SSrd: Mwepụta draịva relay steeti siri ike

2 DC.MA: DC current

3 DC.Vo: DC voltage

0 R/W
7 OP1L OP1 linear mmepụta uru oke dị ala 0.0 ~ OP1H 0.0 R/W
8 OP1H OP1 linear output

high limit value

OP1L ~ 110.0% 100.0 R/W
19 O1FT Mmepụta 1 ọnọdụ mbufe ọdịda 0~1000: 0.0 ~ 100.0 % to continue output 1

control function if the sensor fails, or select OFF (0) or ON (1) for ON-OFF control

0.0 R/W
22 OFST Offset value for P

njikwa

Ala: 0

Elu: 100.0%

25.0 R/W
20 O1HY Output 1 ON-OFF

control hysteresis

Ala: 0.1

Elu: 50.0C (90.0F)

0.5 Celsius C

(0.9 Celsius F)

R/W
23 PL1L MV1 power value

oke ala

Ala: 0

Elu: 50% ma ọ bụ PL1H

0 R/W
24 PL1H MV2 power value limit high Ala: PL1L

Elu: 100%

 

100

 

R/W

25 A1FN Ọrụ mkpu 1 maka mpụta 1 mkpu 0 Ọnweghị: Ọ nweghị ọrụ mkpu

1 dE.HI: Mgbanwe dị elu mkpu

2 dE.Lo: Mgbanwe dị ala

3 db.HI: Deviation band out of band alarm

4 db.Lo: Mgbapụ ngbanwe na mkpu band

5 PV.HI: Usoro uru mkpu dị elu

6 PV.Lo: Usoro uru mkpu dị ala

 

1

 

R/W

Modbus Oke Nkọwa Oke Ọdabara Nweta
 

26

 

A1MD

 

Alarm 1 operation mode

0 NoRM: Omume mkpu nkịtị

1 LtCH: Latching alarm action

2 Jide: Jide mmemme oti mkpu

3 Lt.Ho: Latching & Jide ihe

0 R/W
29 A1HY Alarm 1 Hysteresis control Ala: 0.1

Elu: 50.0°C (90.0°F)

0.1 Celsius C

(0.2 Celsius F)

R/W
34 A1DL Mkpu 1 igbu oge Ala: 0; Elu: 5999 sk 0 R/W
28 A1FT Alarm 1 failure trans- fer mode 0 oFF: OFF if sensor fails

1 on: Gbanye ma ọ bụrụ na ihe mmetụta ada ada

1 R/W
1 A1SP Oti mkpu 1 ebe atọrọ A1FN=PVHI/PVLO

Ala: SP1L Elu: SP1H

100.0 Celsius C

(212.0 Celsius F)

R/W
13 A1DV Alarm 1 deviation value A1FN=DEHI/DELO/DBHI/DBLO

Ala: 0.0 Elu: 500.0°C (900.0°F)

10.0 Celsius C

(18.0 Celsius F)

R/W
33  

A2FN

 

Ọrụ mkpu 2 maka mpụta 2 mkpu

0 Ọnweghị: Ọ nweghị ọrụ mkpu

1 dE.HI: Mgbanwe dị elu mkpu

2 dE.Lo: Mgbanwe dị ala

3 db.HI: Deviation band out of band alarm

4 db.Lo: Mgbapụ ngbanwe na mkpu band

5 PV.HI: Usoro uru mkpu dị elu

6 PV.Lo: Usoro uru mkpu dị ala

7 COMM: RS485

 

2

R/W
 

35

 

A2MD

 

Alarm 2 operation mode

0 NoRM: Omume mkpu nkịtị

1 LtCH: Latching alarm action

2 Jide: Jide mmemme oti mkpu

3 Lt.Ho: Latching & Jide ihe

 

0

 

R/W

36 A2HY Hysteresis control of alarm 2 Obere ala: 0.1°C

Elu: 50.0°C (90.0°F)

0.1 Celsius C

(0.2 Celsius F)

R/W
38 A2DL Mkpu 2 igbu oge Ala: 0; Elu: 5999 sk 0 R/W
37 A2FT Alarm 2 failure forced transfer mode 0 oFF: Alarm output OFF if sensor fails

1 oN: Alarm output ON if sensor fails

1 R/W
2 A2SP Oti mkpu 2 ebe atọrọ A2FN=PVHI/PVLO

Ala: SP1L Elu: SP1H

100.0 Celsius C

(212.0 Celsius F)

R/W
43 A2DV Alarm 2 deviation value A2FN=DEHI/DELO/DBHI/DBLO

Ala: 0.0 Elu: 500.0°C (900.0°F)

10.0 Celsius C

(18.0 Celsius F)

R/W

Communication (CoMM) Parameter

Modbus Oke Nkọwa Oke Ọdabara Nweta
39 ADDR Address assignment of digital
nzikọrịta ozi
Ala: 1

elu: 255

1 R/W
40 BAUD Baud ọnụego nke dijitalụ nkwurịta okwu 0   2.4: 2.4 Kbits/s baud rate

1   4.8: 4.8 Kbits/s baud rate

2   9.6: 9.6 Kbits/s baud rate

3  14.4: 14.4 Kbits/s baud rate

4  19.2: 19.2 Kbits/s baud rate

5  28.8: 28.8 Kbits/s baud rate

6  38.4: 38.4 Kbits/s baud rate

7  57.6: 57.6 Kbits/s baud rate

8  115.2: 115.2 Kbits/s baud rate

2 R/W
41 DATA Data bit count of dig- ital communication 0 7bI: 7 bit

1 8bI: 8 bit

1 R/W
42 PARI The parity bit of digi- tal communication 0 EVEN: Even parity

1  odd: Odd parity

2 NoNE: No parity bit

 

0

 

R/W

Calibration Mode Parameter

Modbus Oke Nkọwa Oke Ọdabara Nweta
52 ADLO mV calibration low

ọnụọgụgụ

Ala: -1999

elu: 1999

 

—-

 

R/W

53 ADHI mV calibration high

ọnụọgụgụ

Ala: -1999

elu: 1999

 

—-

 

R/W

54 RTDL RTD calibration low

ọnụọgụgụ

Ala: -1999

elu: 1999

 

—-

 

R/W

55 RTDH RTD calibration high coefficient Ala: -1999

elu: 1999

 

—-

 

R/W

56 CJLO Cold junction calibra-

tion low coefficient

Ala: -5.00

elu: 40.00

 

—-

 

R/W

Parameter ndị ọzọ

Modbus Oke Nkọwa Oke Ọdabara Nweta
57 CJCT Okpomọkụ Junction Ala: -4000

elu: 9000

—- R
58 ỤBỌCHỊ Ụbọchị Low: 0;

elu: 65535

—- R
59 SRNO Nọmba usoro n'usoro Low: 0;

elu: 65535

—- R
63 CJCL Cold junction low calibration

voltage

Ala: 0

elu: 7552

—- R
69 EROR Koodu mperi Ala: 0; Ọnụ: 65535 —- R
70 MODE Ụdị ọrụ & ọkwa mkpu Ala: 0

elu: 65535

—- R
71 ỌRỤ Device version, firmware version 67.XX —- R
72 CMND Koodu iwu Ala: 0; Ọnụ: 65535 —- R/W
73 JOB1 Koodu ọrụ Ala: 0; Ọnụ: 65535 —- R/W

Koodu mperi

Njehie Koodu Ngosipụta

Akara

 

Nkọwa & Ihe kpatara ya

 

Ndozi Omume

10 ER10 Njehie nkwukọrịta: koodu ọrụ ọjọọ Correct the communication software to meet the protocol

chọrọ

11 ER11 Njehie nzikọrịta ozi: debanye aha adreesị na-enweghị oke Enyela ohu ahụ adreesị akwụkwọ ndekọ aha karịrị oke
14 ER14 Communication error: attempt to write a

read-only data

Edela data naanị ọgụgụ ma ọ bụ data echedoro nye ohu ahụ
15 ER15 Njehie nzikọrịta ozi: dee uru na-enweghị oke na ndebanye aha Edela ihe karịrị oke data na ndekọ ohu
26 ATER Auto-Tuning Error: Failed to perform Auto-Tuning function
  1. The PID values obtained after Auto-Tuning process are out of
    range. Retry Auto-Tuning.
    Auto-Tuning process exceeds 3600 secs
  2. Do not change the setpoint value during Auto-Tuning process.
  3. Use manual tuning instead of Auto-Tuning process.
  4.  Do not set the value as zero for TI & PB.
29 EEPR Enweghị ike ide EEPROM nke ọma Laghachi na onye nrụpụta maka ịrụzi.
30 CJER Ụgwọ nkwụsịtụ oyi maka

Thermocouple adịghị arụ ọrụ

Laghachi na onye nrụpụta maka ịrụzi.
39 SBER Input sensor break Replace the input sensor
40 ADER Ihe ntụgharị A ruo D ma ọ bụ ihe ndị metụtara ya adịghị arụ ọrụ Laghachi na onye nrụpụta izizi maka ndozi.

FAQ

Kedu ka m ga-esi nweta NchNhr njirimara?

To access the User Menu, press the corresponding key on the controller.

Kedu otu m ga-esi mee ka ọnọdụ-emegharị akpaaka?

To activate Auto-Tuning Mode, press and hold a specific key for 5 seconds.

How do I enter Manual Control Mode? To enter Manual Control Mode, press the designated key for 3 seconds. How do I perform calibration? To calibrate a parameter, press and hold the ENTER key for 5 seconds during the calibration procedure.

To enter Manual Control Mode, press the designated key for 3 seconds.

Kedu ka m ga-esi mee nhazi nhazi?

To calibrate a parameter, press and hold the ENTER key for 5 seconds during the calibration procedure.

Akwụkwọ / akụrụngwa

Onye njikwa okpomọkụ Brainchild E62 PID [pdf] Akwụkwọ ntuziaka
E62, QS0E620C, E62 PID okpomọkụ njikwa, E62, PID okpomọkụ njikwa, okpomọkụ njikwa, njikwa

Ntụaka