ABB SACE E2.2H-A

ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP User Manual

Model: SACE E2.2H-A | Brand: ABB

1. Okwu Mmalite na Product Overview

This manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker. Please read this manual thoroughly before any operation.

The ABB SACE EMAX2 E2.2H 1600 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals and a solid-state release in AC EKIP/DIP-LI R 1600. It includes four auxiliary contacts and a circuit breaker in the open-closed position.

Akụkụ ndị bụ isi:

  • Mounting type: Plug-In Mount
  • Voltage: 600.0 volts of alternating current
  • Circuit breaker type: Standard
  • Ogo dị ugbu a: 1600.0 amps
  • Ọnụọgụ mkpanaka: 3
N'ihu view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker

Foto 1: N'ihu view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing the Ekip Touch display, operating buttons (OPEN, Push OFF, Push ON), and the reset mechanism.

2. Ntọala na nwụnye

The ABB SACE EMAX2 E2.2 H 1600 is designed for plug-in mounting. Proper installation by qualified personnel is crucial for safety and optimal performance.

2.1 Mwepu na nyocha

Carefully unpack the circuit breaker and all accessories. Inspect for any signs of shipping damage. Ensure all components listed in the packing slip are present.

ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker inside its wooden shipping crate

Figure 2: The circuit breaker securely packed within its wooden shipping crate, indicating careful handling during transport.

Accessories for the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, including mounting hardware and documentation, in clear plastic bags

Figure 3: Various accessories, such as mounting brackets and additional components, packaged separately for the circuit breaker.

2.2 Na-arịgo

This unit features a plug-in mount design. Refer to the detailed installation diagrams and instructions provided with the product for specific mounting procedures. Ensure the mounting surface is stable and capable of supporting the unit's weight (approximately 105.82 pounds).

2.3 Njikọ eletrik

Connect the main power lines to the designated terminals. The unit is a three-pole breaker. Ensure all connections are secure and comply with local electrical codes and standards.

N'elu view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker showing the three main connection points with copper busbars

Foto 4: Top view illustrating the three main connection points for electrical wiring, designed for robust and secure connections.

Warning: All electrical work must be performed by a qualified electrician. Disconnect all power before installation or maintenance.

3. Ntuziaka ọrụ

The ABB SACE EMAX2 E2.2 H 1600 features an Ekip Touch interface and mechanical push buttons for operation.

3.1 Basic Arụmọrụ

  • To Close (Turn On): Press the "Push ON" button (green). The breaker will close, allowing current flow.
  • To Open (Turn Off): Press the "Push OFF" button (red). The breaker will open, interrupting current flow.
  • Mepee ihe mberede: Use the "OPEN" lever for immediate manual opening.
  • Tọgharia: After a trip event, identify and resolve the cause. Then, press the "Reset" button to reset the tripping mechanism before attempting to close the breaker again.
Close-up of the operating panel of the ABB SACE EMAX2 E2.2 H 1600, showing the 'OPEN' lever, 'Push OFF' (red), 'Push ON' (green) buttons, and 'Reset' button.

Ọgụgụ 5: Zuru ezu view of the operational controls, including the Ekip Touch display and the mechanical buttons for opening, closing, and resetting the breaker.

3.2 Ekip Touch Interface

The Ekip Touch display provides real-time data, settings, and diagnostic information. Refer to the separate Ekip Touch user guide for detailed navigation and configuration instructions.

4. Nlekọta

Regular maintenance ensures the longevity and reliable operation of your ABB SACE EMAX2 circuit breaker. Always disconnect power before performing any maintenance.

4.1 Nlele Oge Nile

  • Visually inspect the breaker for any signs of damage, loose connections, or excessive dust accumulation.
  • Ensure ventilation openings are clear and unobstructed.
  • Check the integrity of all wiring and terminal connections.

4.2 Nhicha

Use a dry, lint-free cloth to clean the exterior surfaces. Do not use abrasive cleaners or solvents. For internal cleaning, consult a qualified service technician.

Akụkụ view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing internal mechanical components and gear assembly

Foto 6: Akụkụ view revealing the intricate mechanical components and gear assembly responsible for the breaker's operation, highlighting areas that may require professional inspection.

4.3 Ọrụ Ndị ọkachamara

Periodic professional servicing by ABB-certified technicians is recommended to ensure optimal performance and compliance with safety standards. This includes checking internal mechanisms and calibration of the Ekip Touch unit.

5. Nchọpụta nsogbu

This section provides general guidance for common issues. For complex problems, contact ABB technical support or a qualified electrician.

5.1 Breaker Trips Frequently

  • Ibu ibu: Check the connected load. Reduce the load if it exceeds the breaker's rated current (1600 A).
  • Circuit dị mkpirikpi: Inspect wiring for short circuits. This requires immediate attention and professional diagnosis.
  • Ground Fault: If applicable, check for ground faults in the system.
  • Ngwa adịghị mma: Disconnect individual equipment to identify a faulty device causing the trip.

5.2 Breaker Does Not Close

  • Steeti Njem: Ensure the breaker is fully reset after a trip. The "DISCHARGED SPRING" indicator might be visible if not reset.
  • Enweghị ike: Verify incoming power supply.
  • Mechanical Obstruction: Check for any physical obstructions preventing the mechanism from closing.
Close-up of the product label on the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing model SACE E2.2H-A, serial number, ratings, and UL Listed certification.

Figure 7: Product label providing critical specifications such as model number (SACE E2.2H-A), serial number, rated maximum voltage, rated short-circuit current, and UL/CSA certifications.

6. Nkọwapụta

Detailed technical specifications for the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker:

NkọwapụtaUru
Product Main TypeSACE Emax 2
Nọmba nlereanyaSACE E2.2H-A
Enyere aha ugbu a (n'ime)1600 A
Ọnụ ọgụgụ okporo osisi3
Ụdị dị ugbu aAC
Ogo Voltage (Ur)690 V
Enyere ọrụ Voltage690V AC
Enyere mkpuchi mkpuchi Voltage (Ui)AC 1000V
Enyere mkpali iguzogide Voltage (Uimp)12 kV (acc. to IEC 60947-2)
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (525 V AC) 85 kA, (690 V AC) 85 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 100 kA, (230 V AC) 100 kA, (380 V AC) 100 kA, (400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (660 V AC) 85 kA, (690 V AC) 85 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100%
Enyere ogo nke obere oge iguzogide ugbu a dị ala Voltage (Icw)for 1 s 85 kA, for 3 s 66 kA
Rated Uninterrupted Current (Iu)1600 A
Igwe ọkụ eletrikUe =<440 V 12000 cycle, Ue = 500 ... 690 V 10000 cycle (30 cycles per hour)
Ịdị ogologo igwe25000 cycle (60 cycles per hour)
Ọnwụ Ike288 W
Akụkụ ngwaahịa15.08 x 12.48 x 16.73 sentimita asatọ
Ibu105.82 pound
Mba onye siỊtali

Note: Specifications are subject to change without notice. Always refer to the product label and official ABB documentation for the most accurate and up-to-date information.

Shipping label for ABB SACE EMAX2 E2.2 H 1600, showing product version, poles, overcurrent release type, and a barcode with the number 8057558336022.

Figure 8: Product identification label, including the EAN/UPC code 8057558336022, which can be used for product verification and lookup.

7. Akwụkwọ ikike na nkwado

For warranty information and technical support, please refer to the official ABB documentation included with your product or visit the official ABB websaịtị.

  • na-alaghachi: This product is eligible for 30-day easy returns. Please check the retailer's return policy for details.
  • Nkwado ndị ahịa: For assistance, contact customer support through your purchase platform or directly via ABB's official channels.
  • ABB Store: You can find more information and products from ABB by visiting the official ABB Store.

© 2024 ABB. All rights reserved. This manual is for informational purposes only.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.